CO-Trust CPU226M 216-1AD33-0X24 PLC is available in Bangladesh
This plc is CO-TRUST PLC CPU226M 216-1AD33-0X24 Compatible of Siemens. Special featurs is 2 PPI port, 14DI/10DO, 72KB Program Memory, 110KB Data Memory, 6.30KHZ high-speed counter
Product details:
- Model : 216-1AD33-0X24
- Power Supply: 220 V AC
- Digital Input: 24
- Digital Output: 16 (Relay)
- Origin: China
- CPU224 AC/DC/Relay
- CO-Trust PLC
- CPU226M 216-1AD33-0X24
Specifictaion | EM223 4 DI / 4 DO, 24V DC |
EM223 8 DI / 8 DO, 24V DC |
EM223
16 DI / 16 DO, 24V DC |
Physical Features | |||
Dimensions(W×H×D) | 46×80×62mm | 71.2×80×62mm | 138×80×62mm |
Power loss(dissipation) | 2W | 3W | 5W |
From +5V (from I/O bus) | 40 mA | 80 mA | 160 mA |
Input Features | |||
Number of integrated inputs | 4 inputs | 8 inputs | 16 inputs |
Input type | Sink/Source(IEC Type 1 sink) | ||
Input Voltage | |||
Maxumum continuous permissible | 30 VDC | ||
Surge | 35 VDC for 0.5 s | ||
Rated value | 24 VDC at 4 mA, nominal | ||
Logic 1 signal(minimum) | 15 VDC at 2.5 mA, minimum | ||
Logic 0 signal(maximum) | 5 VDC ata 1mA, maximum | ||
CO-Trust CPU226M 216-1AD33-0X24 PLC | |||
Optical isolation | 500 VAC for 1 minute | ||
Isolation groups of | 4 points | 4 points | 8 points |
Maximum input delay time | 4.5ms | ||
Connection of 2 Wire Proximity Sensor(Bero) | |||
Premissible leakage current | 1 mA, maximum | ||
Cable Length | |||
Unshielded(not HSC) | 300 m | 3*100 m | 300 m |
Shielded | 500 m | 5*100 m | 500 m |
Number of inputs ON Simultaneously | |||
40ºC | 4 | 8 | 16 |
50ºC | 4 | 8 | 16 |
Output Features | |||
Number of integrated outputs | 4 outputs | 8 outputs | 16 outputs |
Output type | Solid State-MOSFET | ||
Output voltage | |||
Rated Value Permissible Range Logic 1 signal at maximum current Logic 0 signal with 10 kohm load |
24V DC 20.4~28.8V DC 20V DC, minimum 0.1VDC, maximum |
||
Output Current | |||
Number of output | 2 | 4A | 10μA,maximum |
Isolation | 500V AC for 1 minute | ||
In group of | 4 points | 4 points | 4/4/8 points |
Output Delay | |||
Off to On On to Off |
50 μs, maximum 200 μs, maximum |
||
Cable Length | |||
Unshielded | 150 m | ||
Shielded | 500 m |