CJ1W PA202 Omron Power Supply Unit is used to provide power to CJ1M CPUs and I/O units. AC supply versions are available. Clips to the left of the CPU. Also used to power expansion I/O assembly. Equipped with the RUN output for checking the operation status, as well as the replacement notification function for easy maintenance.
Technical data:
Item | Specifications | ||
Model | CJ1W-PA205R | CJ1W-PA205C |
CJ1W-PA202
|
Supply voltage | 100 to 240 V AC, 50/60 Hz | ||
Operating voltage and frequency ranges |
85 to 264 V AC, 47 to 63 Hz | ||
Power consumption | 100 VA max. | 50 VA max. | |
Inrush current *1 | At 100 to 120 V AC: 15 A/8 ms max. for cold start at room temperature At 200 to 240 V AC: 30 A/8 ms max. for cold start at room temperature |
At 100 to 120 V AC:
20 A/8 ms max At 200 to 240 V AC:
40 A/8 ms max. |
|
Output capacity *7
|
5.0 A, 5 V DC | 2.8 A, 5 V DC | |
0.8 A, 24 V DC |
0.4 A, 24 V DC
|
||
Total: 25 W max. |
14 W max.
|
||
Output terminal |
Not provided. | ||
RUN output *2 | Contact configuration: SPST-NO Switch capacity: 250 V AC, 2 A |
Not provided. | |
Replacement notification function |
Not provided. | With Alarm output 30 V DC max., 50 mA max. |
Not provided.
|
Insulation resistance | 20 MΩ min. between AC external and GR terminals *3 |
20 MΩ min. between external terminals and GR terminal *3,20 MΩ 1 min. between alarm output terminals and GR terminal *3. |
20 MΩ min.
between AC external and GR terminals *3 |
Dielectric strength *4
|
2,300 V AC 50/60 Hz for 1 min between AC external and GR terminals *3 Leakage current: 10 mA max. |
2,300 VAC, 50/60 Hz for 1 min between external terminals and GR terminal *3 and1,000 V AC, 50/60 Hz for 1 min between alarm output terminals and GR terminal *3 with a leakage current of 10 mA |
2,300 V AC 50/60 Hz for 1 min
between AC external and GR terminals *3 Leakage current: 10 mA max. |
Leakage current: 10 mA max. | |||
Noise immunity |
2 kV on the power supply line | ||
Vibration resistance | Conforms to IEC60068-2-6 5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz Acceleration of 9.8 m/s2 for 100 min in X, Y, and Z directions |
||
Shock resistance | Conforms to IEC60068-2-27 147 m/s2, 3 times in X, Y, and Z directions |
||
Ambient operating temperature |
0 to 55 °C | ||
Ambient operating humidity |
10% | 10% *5 |
90%
|
Atmosphere | Must be free from corrosive gases. | ||
Ambient storage temperature |
from – 20 to 70 °C | – 20 to 75 °C *5 |
– 20 to 75 °C
|
Grounding | Less than 100 Ω | ||
Enclosure | Mounted in a panel. | ||
Weight | 350 g max. | 400 g max. | 200 g max. |
Power consumption: 50 VA maximum.
Inrush current *1: At 100 to 120 V AC: 20 A/8 ms max. for the cold start at room temperature
At 200 to 240 V AC: 40 A/8 ms max. for the cold start at room temperature
Output capacity *7: 2.8 A, 5 V DC 0.4 A, 24 V DC Total: 14 W maximum.
Dielectric strength *4: 2,300 V AC 50/60 Hz for 1 min between AC external and GR terminals *3 Leakage current: 10 mA max.
Ambient operating humidity: 90%