Unimat High-performance Inverter 5.5KW Single Phase Input FA200-5.5G-S2
Variable Frequency Inverter-VFD:
- Unimat High-performance Inverter 5.5KW Single Phase FA200-5.5G-S2
- The encoder vector control, torque response speed≤20ms
- No encoder vector control, torque control accuracy.
- No encoder vector control, 150% rated torque at 1Hz
- Widely voltage range and allowable voltage swing range
- High overload capacity, 150% rated currency 60 seconds
- Rated currency 2 seconds, 200% instantaneous trip
- Long-life components design to extend the product usage life
- Compact structure design to adapt different load operations
- Independent air-duct design to improve anti-dust capacity can be installed penetrably, higher adaptability
- Removable DC FAN to ensure system run stably and easy to wash and maintenance
- The keyboard is plug-and-play, support leading out to outside, support data copy
Product Specification:
Model | FA200-5.5G-S2 |
Product name | Unimat Variable Frequency Drive |
Brand | Unimat |
Country of origin | Japan |
Power Capacity | 5.5kw |
Inverter Capacity (kVA) | 6.875 |
Rated Output Current (A) | 25 A |
Max. Output Voltage | 400 VAC |
Max. Output Frequency (Hz) | 400 Hz (Programmable) |
Rated Input Voltage and Frequency | 3-phase, 380 to 440V, 50/60Hz |
Allowable Voltage Fluctuation | -15 to +10% |
Allowable Frequency Fluctuation | ±5% |
Control Method | Sine wave PWM (V/f control) |
Frequency Control Range | 0.1 to 400Hz |
Frequency Accuracy (Temperature Change) | Digital reference: ±0.01% |
Frequency Setting Resolution | Digital reference: 0.1Hz (less than 100Hz) |
Output Frequency Resolution | 0.01Hz |
Overload Capacity | 150% rated output current for one minute |
Frequency Reference Signal | 0 to 10VDC (20kΩ), 4 to 20mA (250Ω), 0 to 20mA (250Ω) Frequency setting volume (Selectable) |
Accel/Decel Time | 0.1 to 999 sec. (accel/decel time are independently programmed) |
Braking Torque | Short-term average deceleration torque |
V/f Characteristics | Possible to program any V / f pattern |
Motor Overload Protection | Electronic thermal overload relay |
Instantaneous Over Current | Motor coasts to a stop at approx. 200% of inverter rated current |
Overload | Motor coasts to a stop after 1 minute at 150% of inverter rated output current |
Over Voltage | Motor coasts to a stop if DC bus voltage exceed 820V |
Under Voltage | Stops when DC bus voltage is approx. 400V or less |