CJ1W-ID211 Omron Input Unit-Module technical data:
Brand Name | Omron |
Model Number | CJ1W-ID211 |
I/O points | 16 inputs |
Input voltage and current | 24 VDC, 7 mA |
Commons | 16 points, 1 common |
External connection | Removable terminal block |
Input Impedance | 3.3 kΩ |
ON Voltage/ON Current | 14.4 VDC min |
OFF Voltage/OFF Current | 5 VDC max./1 mA max. |
Number of Circuits | 16 points/common, 1 circuit |
CJ1W-ID211 Omron Input Unit-Module-
Name |
8-point Triac Output Unit with Terminal Block
|
Model | CJ1W-OA201 |
Max. Switching Capacity |
0.6 A 250 VAC, 50/60 Hz
|
Max. Inrush Current |
15 A
|
Min. Switching Capacity | 50 mA 75 VAC |
Leakage Current |
1.5 mA max.
|
Residual Voltage | 1.6 VAC max. |
ON Response Time | 1 ms max. |
OFF Response Time |
1/2 of load frequency + 1 ms or less.
|
Number of Circuits |
8 points
|
Surge Protector |
C.R Absorber + Surge Absorber
|
Fuses |
5 A
The fuse cannot be replaced by the user. |
Insulation Resistance |
20 MΩ between the external terminals and the GR terminal.
|
Dielectric Strength |
2,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
|
Internal Current Consumption | 220 mA max. |
Weight | 150 g max. |
technical data of (16-points)
Name |
16-point Contact Output Unit with Terminal Block
|
Model | CJ1W-OC211 |
Max. Switching Capacity |
2 A 250 VAC, 2 A 24 VDC (8 A/Unit)
|
Min. Switching Capacity | 1 mA 5 VDC |
Relays |
NY-24W-K-IE Cannot be replaced.
|
Service Life of Relay |
Mechanical: 20,000,000 operations
Service life will vary depending on the connected load. |
ON Response Time | 15 ms max. |
OFF Response Time | 15 ms max. |
Number of Circuits |
16 points/common, 1 circuit
|
Insulation Resistance |
20 MΩ between external terminals and the GR terminal
|
Dielectric Strength |
2,000 VAC between the external terminals and the GR terminal
|
Internal Current Consumption |
110 mA 5 VDC max.
96 mA 24 VDC max. |