FX2N-4DA-Mitsubishi Module-Digital to Analog-Converter.
Technical data:
Item |
Specification |
Analog circuits | 24V DC ± 10%, 55mA |
Digital circuits | 5V DC, 30mA |
Isolation |
Photo-coupler isolation between analog and digital circuits. DC/DC converter isolation of power from the main unit.
No isolation between analog channels. |
Number of occupied I/O points |
The analog block occupies 8 points. (can be either inputs or outputs)
|
Item
|
Voltage input |
Current input
|
Either voltage or current input can be selected with your choice of input terminal. Up to four input points can be used at one time. | ||
Analog input range | DC -10V to +10V this unit may be damaged by an input voltage in excess of ± 15V. |
DC -20mA to +20mA
this unit may be damaged by an input current in excess of ± 32mA. |
Digital output | 12-bit conversion stored in 16-bit 2’s complement form. Maximum value: +2047 Minimum value: -2048 | |
Resolution | 5mV (10V default range 1/2000) |
20mA (20mA default range 1/1000)
|
Overall accuracy | ± 1% (for the range of -10V to +10V) |
± 1% (for the range of -20mA to +20mA)
|
Conversion speed | 15ms/channel , 6ms/channel |
Item |
Specification |
General specifications | Same as those for the main unit |
Dielectric withstand voltage |
500V AC, 1min
|
Mitsubishi FX2N 4DA analog output modules give the user with four analog outputs. FX0N/FX2N controller to the analog signals needed by the process and the modules convert digital values from the model part. The modules can output both electricity and voltage signals With 4 analog output channels. It needs a separate 24Vdc power source.
Products FX1S, FX1N, and FX2N PLC specified. These are DIN rail mounts and are 90(mm) maximum and 87(mm) so deep. FX2N-4DA-Mitsubishi Module-Digital to Analog-Converter.
The FX2n-4DA analog special function block has 4 analog output signal channels. The output channels 2N take a digital value and output analog signal. This is known as a D/A conversion. TheFX2n-4DA has a max resolution of twelve bits. The selection voltage i/o is by user wiring. Analog ranges of -10 to 10VDC and 0 to 20mA may be selected for each channel.